Sensing Element Range Accuracy
• Temperature with any Option (excluding Humidity) -4°
to 122° F (-20° C to 50° C) ±0.35° F (0.2° C)
• Temperature with Humidity and any Option 50° F to
104° F (10° C to 40° C) ±0.5° F (0.3° C)
• Humidity 20% to 80% ±2% typical
• CO2 400 to 1250 PPM ±30PPM or +/-3% (greater of
two) 1250 to 2000 PPM ±5% of reading plus 30 PPM
• VOC 0 to 2,000 PPM ±100 PPM
CLIMATEMASTER ASW016STC, ZS2, WALL THERMOSTAT, TEMPERATURE SENSOR, STD FOR MPC
Out of Stock$142.00
Out of stock
Description
Application: ASW sensors are wall-mounted temperature sensors for use with the MPC controller on Water-to-Air units. The ASW is available in 3 different models to allow for application flexibility. Features such as room temperature sensing, digital LCD readout, set point adjustment, override push button, heat pump reset, lockout recognition, fault type, LED indicator, cosmetics and occupancy status can be supplied by the different types of ASW wall sensors. The ASW wall mounted sensors are low profile, which provides a distinguished look for building architects and engineers.
Wiring: PREREQUISITE: The RNet cable is wired to the controller. The shield wire and the ground wire should be inserted into the controller’s GND terminal, insert the other 4 wires into the RNet Sensor’s screw terminal connector. If wiring 2 cables, insert like colored wires into each terminal. It is recommended that you use the following RNet wiring scheme: Connect this wire… To this terminal… Red +12V, Black RNet-, White RNet+, and Green Gnd.
Power Requirements Sensor Type Power Required: • Temperature Only All Models 12 Vdc @ 8 mA Temperature with Humidity • Temp with VOC, or Temp/VOC/Humidity All Models 12 Vdc @ 60 mA • Temp with CO2 , or Temp/ CO2 /Humidity All Models 12 Vdc @ 15 mA (idle) to 190 mA (CO2 measurement cycle).
Power Supply: controller supplies the Rnet sensor network with 12 Vdc @ 210 mA: • Additional power may be required. See sensor power requirements above.
Communication: • 115 kbps Rnet connection between sensor(s) and controller 15 sensors max per Rnet network; 5 sensors max per control program.
Local Access Port: • For connecting a laptop computer to the local equipment or WebCTRL® network for maintenance and commissioning.
Environmental Operating Range: • 32° to 122° F (0° – 50° C), 10% to 90% relative humidity, non-condensing.
Mounting Dimensions: • Standard 4”x 2” electrical box using provided 6/32” x 1/2” mounting screws.
Overall Dimensions: • Width: 2.75” (6.99 cm) Height: 4.75” (12.07 cm) Depth: 13/16” (2.01 cm).
Additional information
Brand | ClimateMaster |
---|---|
Description | Parts – OEM |